#Drive wiring
- Make sure you have the right fuses
- Internal schematic diagram
- Lists of internal Wireing
- External schematic diagram (student connections)
- Make sure the burden resistor jumper is in the right position
- Links to hardware files, spec sheets etc…
#Parameter Changes
####CONFIGURATION/DRIVE PERSONALITY/Iarm BURDEN OHMS
- PIN680 to ‘110.44’
- Reduce the model (plx15) rating by 50% so it works with the 2HP
motor
- follow procedures on page 198 of the user
manual
- Note. After parameter PIN680 (Iarm BURDEN OHMS) has been altered, it
will only apply after the following:
- Save the new value using the PARAMETER SAVE function.
- Turn the unit control supply off then back on again.
- Adjust- 2)RATED ARM AMPS parameter in the CALIBRATION menu, first to
its maximum setting (100%), and then to its minimum setting (33%), (Note
that the values are 100% Amps, 33% Amps, of new ratings with changed
burden). Finally return it to the desired value for your motor.
- Save the new desired 2)RATED ARM AMPS parameter with another
PARAMETER SAVE.
####CHANGE PARAMETERS/FIELD CONTROL/FIELD ENABLE
- PIN99 to ‘DISABLE’
- Using Permanent Magnet DC machine, so field needs to be
disabled
####CHANGE PARAMETERS/CALIBRATION
- PIN2 to ‘9.6’ (/RATED ARMATURE AMPS)
- PIN3 to ‘100.00’ (/CURRENT LIMIT (%))
- PIN4 to ‘2.00’ (/RATED FIELD AMPS) - N/A - field is
disabled
- PIN5 to ‘1800’ (/BASE RATED RPM)
- PIN6 to ‘1800’ (/DESIRED MAX RPM rpm)
- PIN7 to ‘0.00’ (/ZERO SPEED OFFSET)
- PIN8 to ‘60.00’ (/MAX TACHO VOLTS)
- PIN9 to ‘ARMATURE VOLTS (AVF)’ (/SPEED FBK
TYPE)
- (/ENCODER SCALING)
- PIN10 to ‘DISABLED’ (/QUADRATURE
ENABLE)
- PIN11 to ‘1000’ (/ENCODER LINES)
- PIN12 to ‘1.0000’ (/MOT/ENC SPD RATIO)
- PIN13 to ‘NON-INVERT’ (/ENCODER SIGN)
- PIN14 to ‘4.32’ (/IR COMPENSATION)
- PIN15 to ‘1.0000’ (/FIELD CUR FB TRIM)
- PIN16 to ‘1.0000’ (/ARM VOLTS TRIM)
- PIN17 to ‘1.0000’ (/ANALOG TACHO TRIM)
- PIN18 to ‘185.1’ (/RATED ARM VOLTS)
- PIN19 to ‘208.0’ (/EL1/2/3 RATED AC )
- PIN20 to ‘1’ (/MOTOR 1,2 SELECT)
####CHANGE PARAMETERS/CURRENT CONTROL
- PIN93 to ‘10.00’ (/CUR PROP GAIN)
- PIN94 to ‘1.00’ (/CUR INT GAIN)
- PIN95 to ‘56.50’ (/CUR DISCONTINUITY)
####DISPLAY FUNCTIONS/REDUCED MENU ENABLE
####DISPLAY FUNCTIONS/PASSWORD CONTROL/ALTER PASSWORD
####PARMETER SAVE
Storing the altered values in the drive so that they are retained
when the control supply is removed. This is achieved by travelling to
the PARAMETER SAVE location in the main menu. Press the right key to
enter the PARAMETER SAVE window. Once there, using the UP key saves all
the presently prevailing parameter values. The bottom line of the
display will read SAVING and then FINISHED. If you wish to abandon
changes made since the last save, simply remove the control supply
WITHOUT having performed parameter save.